AbstractIn this paper, the structure, modeling, parameter design, and control method are proposed for a new hybrid structure of a static var compensator in parallel with a hybrid active power filter (SVC//HAPF). The SVC part of the SVC//HAPF is used to dynamically compensate the reactive power. And, the HAPF part is used to provide harmonic power and small amount of reactive power compensation. Due to the large fundamental voltage drop on coupling the LC part, the active inverter part of the SVC//HAPF has low voltage rating. Meanwhile, the parallel-connected SVC acts as a current divider to reduce the active inverter current. Therefore, the proposed SVC//HAPF shows the great promise in compensating harmonic current and wide-range reactive power with a low (both) voltage and current rating active inverter part. To show the advantages of the proposed SVC//HAPF, simulation comparisons among the active power filter (APF), HAPF, SVC in series with HAPF (SVC−HAPF), and the proposed SVC//HAPF are provided. Finally, experimental results based on the laboratory-scaled hardware prototype are given to show the validity of the SVC//HAPF.
KeywordActive power filter (APF) harmonic current compensation hybrid APF (HAPF) reactive power compensation static var compensator (SVC)
Language英語English
The Source to ArticlePB_Publication
PUB ID37194
Document TypeJournal article
CollectionUniversity of Macau
Corresponding AuthorLam, C. S.
Recommended Citation
GB/T 7714
Wang, L.,Lam, C. S.,Wong, M. C.. Hybrid structure of static var compensator and hybrid active power filter (SVC//HAPF) for medium voltage heavy loads compensation[J]. IEEE Transactions on Industrial Electronics, 2018, 4432-4442.
APA Wang, L.., Lam, C. S.., & Wong, M. C. (2018). Hybrid structure of static var compensator and hybrid active power filter (SVC//HAPF) for medium voltage heavy loads compensation. IEEE Transactions on Industrial Electronics, 4432-4442.
MLA Wang, L.,et al."Hybrid structure of static var compensator and hybrid active power filter (SVC//HAPF) for medium voltage heavy loads compensation".IEEE Transactions on Industrial Electronics (2018):4432-4442.
Files in This Item:
There are no files associated with this item.
Related Services
Recommend this item
Bookmark
Usage statistics
Export to Endnote
Google Scholar
Similar articles in Google Scholar
[Wang, L.]'s Articles
[Lam, C. S.]'s Articles
[Wong, M. C.]'s Articles
Baidu academic
Similar articles in Baidu academic
[Wang, L.]'s Articles
[Lam, C. S.]'s Articles
[Wong, M. C.]'s Articles
Bing Scholar
Similar articles in Bing Scholar
[Wang, L.]'s Articles
[Lam, C. S.]'s Articles
[Wong, M. C.]'s Articles
Terms of Use
No data!
Social Bookmark/Share
All comments (0)
No comment.
 

Items in the repository are protected by copyright, with all rights reserved, unless otherwise indicated.